FALCON 1000

Falcon 1000 range of SCR/IGBT based rectifier Industrial UPS systems are designed for the industrial application. Built for working reliably in harsh environmental conditions with IP31 and above with high operating temperatures.

Suitable for Oil & Gas, Cement plants, Thermal Power plants and manufacturing facilities.

Technical Specifications

Input   Options
Nominal Voltage 415 VAC (3 Ph+ N), +/- 15% 440V, 20%
Frequency 50 Hz,+/- 6% 60Hz
Rectifier Bridge Configuration 6 Pulse APFC 12 pulse
Power Factor > 0.92 0.99
ITHD < 30% < 3%
    Input Source Selector
Battery
Nominal DC Up to 15f0/ A – 240V DC, 20f0/ A & above – 360V DC 11 ov upto 20kVA
220V upto 60kVA
Charging Current 10A for 5-20kVA, 15A for 25-30kVA, 20A for35-60kVA @40% Additional Rating for Charging
DC Ripple 2% without Battery / 1 % with Battery  
Type SMF / Lead acid / Ni – Cd  
Configuration Individual / Common Battery Common DC Bus
    Battery Temp Compensation
Output
Nominal Rating (f0/A) 5 10 15 20 25 30 35 40 50 60  
Nominal Power f<:!N at 0.8 PF 4 8 12 16 20 24 28 32 40 48 Uptp 180
Voltage 220V/230V/240V AC 11 OV upto 80 f0/ A
Voltage Stability Steady state+/- 1 % 2% for 110V
Dynamic Response For O to 100% step load change the output shall remain within + 5% & recover to 98% within one cycle. ( IEC 62040-3, Class 1)  
Frequency 50 Hz,+/- 0.1% 60Hz
Voltage distortion at linear load <=2%  
Voltage distortion at non-linear load <= 5% (Ref 62040-3)  
Waveform Sinusoidal  
Topology IGBT Based DSP Control  
Power Factor 0.6 to unity within f0/ A & f<:!N rating  
Crest Factor 3:1  
Overload Capacity from Inverter at Nominal Voltage 110% for 60 min, 125% for 10 min, 150% for 60 sec 125% for 15 min, 300% for 4mS
Overload Capacity from Inverter at Nominal Voltage 110% for 60 min, 125% for 10 min, 150% for 60 sec 125% for 15 min, 300% for 4mS
Configuration Stand Alone, Parallel Redundant Hot standby