The Falcon 7000 range of VFI (double conversion mode) Three Phase Online UPS from 25 – 900 KVA is the first high power, transformer free UPS which has been designed specifically for the harsh power and site conditions found in India and other emerging markets.
Frame Capacity | 150 KVA | 250 KVA | 180 KVA | 300 KVA |
Capacity | 25-150KVA | 25-250KVA | 30 -180KVA | 30-300KVA |
Power Module Type | 25KVA | 25KVA | 30KVA | 30KVA |
Input | ||||
Phase | 3 Phases+Neutral+Ground | |||
Voltage | 400/415V | |||
Frequency | 50/60Hz | |||
Power Factor | >0.99 | |||
THDi | THDi < 3% | |||
Voltage Range | – 25% to + 15% @ 100% Load | |||
– 45% to + 15% @40% Load | ||||
Output | ||||
Voltage | 400/415V | |||
Voltage Regulation | +/-1% | |||
THDu | THD | |||
Power Factor | 1.0 | 0.9 | ||
Crest Factor | 3:1 | |||
Overload Capability | 110% for 1 hour; 125% for 1 O minutes ;150% for1 minute; > 150% for 200ms | |||
Battery | ||||
Voltage | 40 Battery System. | |||
Charger Power | 20% of System Power | |||
System | ||||
System Efficiency | Online mode: upto 96%; ECO mode: upto 99% | |||
Display | 10.4″ LCD+LED, Colour Touch Screen +Keyboard | |||
Interface | Standard: RS232, RS485, Dry contacts, USB, Optional: SNMP, Expansion dry contact card. |
|||
Operation Temperature | 0~40 deg C | |||
Storage Temperature | -40~70 deg C | |||
Relative Humidity | 0~95%(non -condensing) | |||
Noise | 72dB@ 100% load, 68dB@ 45% load (1 meter away) | |||
Altitude of Operation | s1000, load deration for higher altitude. | |||
Physical | ||||
Cabinet | ||||
Dimension (W’D*H)(mm) | 600 X 1100 X 1600 | 600 X 1100 X 2000 | 600 X 1100 X 1600 | 600 X 1100 X 2000 |
Weig ht in Kgs – Ca bi net without Power Modules | 170 Kgs | 220 Kgs | 170 Kgs | 220 Kgs |
Weight in Kgs – Power Modules | 32Kgs | 34Kgs | ||
Protection class | IP20 | |||
Colour | Black | |||
Applicable Standards | ||||
Safety | IEC 62040-1 | |||
EMC | IEC 62040-2 | |||
Performance | IEC 62040-3 |