Falcon 8500 range of Three Phase Online UPS systems are designed, for the data security and business continuity of today’s networked and cloud environment. Its unique modular design and compact footprint comes with variety of special features which are uncommon in this category of UPS Systems.
Rating in KVA | 30 | 40 | 60 | 80 | 120 | 160 |
Input | ||||||
Nominal Voltage | 415 V AC 3 ph + N (± 15%) | |||||
Nominal frequency | 50 Hz (46 to 54Hz) | |||||
Topology | 32 bit DSP controlled | |||||
Battery Voltage | 384 V DC | 480 V DC | ||||
Output | ||||||
Power in KW | 24 | 32 | 48 | 64 | 96 | 128 |
Power Factor | 0.6 to Unity within KVA and KW rating | |||||
Voltage | 400 V / 415 V AC (± 1%) 3 Ph (380V/ 440 V Optional) | |||||
Frequency | 50 Hz (± 0.1 Hz) | |||||
Transient Response | ± 5%, recovery within one cycle to 98% | |||||
Waveform | Sinusoidal | |||||
Total Harmonic Distortion | < 1% max for Linear Load, < 3% max for Non-Linear Load (Ref IEEE 62040-3) |
|||||
Overload Capacity | 110% for 60 min, 125% for 10 min, 150% for 60 sec | |||||
Inverter Efficiency (Ref. IEC 60146-1-1) | up to 93% | up to 94% | ||||
Bypass | ||||||
Voltage & Frequency | 415 V AC , ±15%, 50 Hz (± 2.5%) | |||||
Transfer Time | Synchronous mode : No break, Asynchronous mode < 10 ms |
|||||
Manual Bypass | Provided | |||||
Environment | ||||||
Operating Temperature | 0 to 40° C | |||||
Storage Temperature | 0 to 70° C | |||||
Relative Humidity | up to 95% RH (Non-condensing) | |||||
Maximum Operating Altitude | 1000 m (without de-rating) | |||||
Acoustic Noise @ 1m (Ref. ISO 3746) | < 65 dBA | < 68 dBA | ||||
Enclosure Protection Grade | IP 20 | |||||
Ventilation | Forced air cooling | |||||
Cable Entry | Bottom | |||||
Dimensions in mm | ||||||
Width | 600 | 800 | 1000 | 1200 | ||
Depth | 800 | 800 | 900 | 1000 | ||
height | 1750 | 1750 | 1750 | 1750 | ||
Cabinet Finish | RAL 7016, Texture Finish | |||||
Testing Standards | IEC 62040-3 | |||||
Communication | ||||||
Interface & Protocol | Intelligent RS 232 | |||||
Available Options | SNMP, MODBUS, Web based monitoring |