Messung Electrical Engineering

ups manufacturers in india

FALCON X5

Fuji Electric’s Falcon X5 Series is an unique and innovative UPS with competitive benefits of low ownership cost,
high efficiency and is designed to operate in harsh environments with higher availability.

Features & Benefits

  • Flexibility
    • Common battery option for optimised selection of Battery for multiple UPS in parallel or Independent Configrations
    • Wide input voltage from +20% to -40%
    • Genset compliant with adaptive progressive walk-in and rectifier delay start options
    • 3 Phase 3 wire rectifier fully compatible with existing infrastructure
    • Compatible with all types of industrial loads including regenerative loads
    • Parallel upto 8 units for capacity or redundancy
  • Reliability
    Operating temperature of 0-40°C with special attention in component selection and design to improve reliability
    • Input Phase sequence correction provided as standard
    • Advanced battery management techniques to improve battery life with three stage charging and auto equalizing charge at pre-defined intervals.
    • Monitoring runtime of critical components, such as fans, capacitors, batteries for predective life estimation
  • Total Cost of Ownership
    • Efficiency of upto 95.5% in online double conversion mode of operation with in-built isolation transformer
    • Intelligent Eco Mode of Operation with an efficiency of upto 99%

Technical Specifications

UPS Rating (KVA)100210160200250300
UPS Rating (KW)90108144180225270
Input Parameters  
Rated Voltage400 V, 3 Phase + PE
Rated Voltage Tolerance+20%, -40%*
Rated Frequency50/60 Hz
Current Harmonic Distortion (THDi) **< 3% at load 100%>
Bypass Parameters  
Rated Voltage400 V ± 10%, 3 Phase + N + PE
Rated Frequency50 or 60 Hz (Configurable)
Output Parameters  
Rated Voltage400 V (Settable 380/415 V), 3 Phase + N + PE
Rated Frequency50 or 60 Hz (Configurable)
Voltage Variation – Static load±1%
Crest Factor3:1
Voltage Distortion at Linear Load≤1% (Typical)
Voltage Distortion at Non-Linear Load (as per IEC62040)≤3%
Frequency Stability with Inverter Synchronized to The By-Pass Mains±2% (Settable from ±1% to ±6%)
Voltage Phase Shift with Balanced and UnBalanced Load120 ± 1°
Overload Capacity at 40°C110% for 60 mins, 125% for 10mins, 150% for 1min
Load Power Factor0.7 Leading to 0.5 Lagging without Derating
EfficiencyUpto 99% in Eco Mode and upto 95.5% in Online Mode
Battery Parameters 
Nominal Battery Voltage480 Vdc
CompatibilityCompatible with SMF, Tubular, Ni-Cd, Li -Ion Battery
Environmental Parameters 
Ambient Temperature for the UPS0 to 40°C
Range of Relative Humidityupto 95% max (without Condesing)
Maximum Operating AltitudeUp to 1000 above MSL
Storage TemperatureFrom -25°C up to 60°C (UPS))
Acoutic Noise at 1m from Panel Front (Ref ISO3746)< 65 dba
Mechanical Parameters 
Dimension(W*D*H in mm)840*900*18001000*1000*20001200*1000*2050
Weight in Kgs(Approx)900kgs1200kgs1400kgs