Messung Electrical Engineering

ups manufacturers in india

FALCON X7

Fuji Electric’s Falcon X7 Series is an unique and innovative UPS with competitive benefits of low ownership cost, high efficiency and is designed to operate in harsh environments with higher availability.

Features & Benefits

  • Flexibility
    Flexible configuration for optional inbuilt transformer
    Compatible with multiple battery technologies including Lithium Ion batteries
    Common battery option for optimised selection of Battery for UPS in parallel or Independent configurations
    Wide input voltage from +20% to -40%
    Genset compliant with adaptive progressive progressive walk-in and rectifier delay start options
    3 Phase 3 wire rectifier fully compatible with existing infrastructure
    Parallel upto 8 units for capacity or redundancy
  • Reliability
    Operating temperature of 0-40oC with special attention in component selection and design to improve reliability
    Input phase sequence correction provided as standard
    Advanced battery management techniques to improve battery life with three stage charging and with auto equalizing charge at predefined intervals
    Monitoring runtime of critical component such as fans, capacitors, batteries for predictive life estimation
  • Total Cost of Ownership
    Efficiency of upto 96.5% in online double conversion mode
    Intelligent Eco mode operation with an efficiency of upto 99%

Technical Specifications

UPS Rating (KW)100120160200250300400500600
Input Parameters  
Rated Voltage400 V, 3 Phase + PE
Rated Voltage Tolerance+20%, -40%*
Rated Frequency50/60 Hz
Current Harmonic Distortion (THDi) **< 3% at load 100%>
Bypass Parameters  
Rated Voltage400 V ± 10%, 3 Phase + N + PE
Rated Frequency50 or 60 Hz (Configurable)
Output Parameters  
Rated Voltage400 V (Settable 380/415 V), 3 Phase + N + PE
Rated Frequency50 or 60 Hz (Configurable)
Voltage Variation – Static load±1%
Crest Factor3:1
Voltage Distortion at Linear Load≤1% (Typical)
Voltage Distortion at Non-Linear Load (as per IEC62040)≤3%
Frequency Stability with Inverter Synchronized to The By-Pass Mains±2% (Settable from ±1% to ±6%)
Voltage Phase Shift with Balanced and UnBalanced Load120 ± 1°
Overload Capacity at 40°C110% for 60 mins, 125% for 10mins, 150% for 1min
Load Power Factor0.7 Leading to 0.5 Lagging without Derating
EfficiencyUpto 99% in Eco Mode and upto 95.5% in Online Mode
Battery Parameters 
Nominal Battery Voltage480 Vdc
CompatibilityCompatible with SMF, Tubular, Ni-Cd, Li -Ion Battery
Environmental Parameters 
Ambient Temperature for the UPS0 to 40°C
Range of Relative Humidityupto 95% max (without Condesing)
Maximum Operating AltitudeUp to 1000 above MSL
Storage TemperatureFrom -25°C up to 60°C (UPS))
Acoutic Noise at 1m from Panel Front (Ref ISO3746)< 65 dba
Mechanical Parameters 
Dimension(W*D*H in mm)840*900*18001000*1000*20001200*1000*20001700*1000*2000
Weight in Kgs(Approx)       400         850          900110013001400

Downloads